B:Electrical Tests (Pre-Energization Verification)

Mar 25, 2025

Insulation Resistance Test (Megger Test)

Measure winding-to-ground & winding-to-winding insulation resistance.

Minimum acceptable value: >1 MΩ (typically much higher for new units).

Winding Resistance Test (DC Resistance)

Ensure balanced resistance across all phases (compare with factory data).

Turns Ratio Test (TTR Test)

Confirm correct voltage ratio (matches nameplate).

Polarity & Phase Sequence Check

Verify correct phase rotation (A-B-C sequence) for parallel operation.

Dielectric Withstand Test (HiPot – Optional)

If required, perform a power-frequency withstand test (2 × rated voltage + 1 kV for 1 min).